Diesel
Driven Genset
Click to enlarge ->
Standard
Delivery:
-
Diesel
engine 1 set
-
Alternator 1
set
-
Radiator
and pusher fan 1 set
-
Control
panel 1 set
-
Skid
of engine and alternator 1 pcs
-
Governor
(Mechanical governor) 1 pcs
-
Starter
motor 1 set
-
Battery
charging alternator 1 set
-
Starter
battery 1 set
-
Silencer
loose 1 set
-
Operation
& maintenance manual 1 copy
-
Rubber
cushion 1 set
-
Spare
parts box 1 set
1.
Working Condition:
2.
Standard:
Applicable
codes and standards
-
Genset
ISO8528、GB2820-97、YD/T
502-2000
-
Alternator
GB755、BS5000、IEC34、CSA
C22.2-100 MG1-32、VDE0530、NEMA、EN60034
-
Engine
ISO3046、BS5514
-
Noise
level The noise level should 105db(A) at 7m
3.
Technical Data:
1)
General construction
-
Genset
model: 16GF
-
Standby
rated: 22KVA
-
Prime
rated: 20KVA
-
Current:
28.9A
2)
Gensets power output:
10-1000KW
diesel generator sets can output the rated power in compliance with
GB2820-97 under the condition
below:Temperature:25C,Altitude:<1000m(above sea
level),Barometer:760mm,Humidity:60% at 25C.
If
the operation condition exceeds the above-mentioned requirements,
the generating sets output should be corrected in compliance with
following requirements, Diesel engine output should be modified in
compliance with item below. Alternator engine output should be
modified according to GB755-81, “Alternator Basic Technical
requirement”.
When
the generating set is operated under the condition of less than
1500m set level of altitude and less than 38C of environment
temperature, it is allowed to run at 110% overload, but the
operation time should not exceed one hour.
Diesel
engine can output the rated power if the engine operates under 2250m
sea level and 38C of environment temperature. No need for adjusting
fuel system when the engine operates under rated load. If the
altitude is above 2250m,the power output will be reduced by 4% for
every 300m.If the environment temperature is exceeded 38C,the power
output will be reduced by 2% for every 11C.If the set operates under
the above conditions, the fuel system should be adjusted to reduce
fuel supply, the power output of the generator set will be reduce
also.
3)
Genset data:
-
Rated
Voltage 400/230V,3
Phase
-
Rated
frequency 50Hz
-
Power
factor 0.8PF(Lag)
-
Phase
number 3 Phase 4 wire
-
Rotating
Speed 1500r.p.m
-
Speed
adjustment Mechanical governor
-
Starting
method Manual
-
Starting
device Electric
-
Starting
Voltage 12 DC electric starter
-
Starting
time Within 8-15s (To full voltage under no load)
-
cooling
system Water cooling method
-
The
following table shows the 8characterstics of voltage and
frequency of the genset:
|
type |
voltage |
frequency |
|
Regulation
rate at steady (%) |
+/-1.0 |
0-5
, Adjustable |
|
Regulation
rate transient state(%) |
+20
~ -15 |
+/-
10 |
|
Stabilization
time(S) |
<+/-
1S |
<5S |
|
Fluctuation
rate(%) |
0.5 |
0.5 |
4)
Diesel Engine:
-
Engine
model D226B-3
-
Engine
manufacture Weichai DEUTZ
-
Continuous
power 37.5KVA
-
Number
of cylinders 3
-
Rated
speed 1500r.p.m
-
Bore*Stroke
105*120mm
-
Full
oil system Full oil strainer
-
Lube
oil system Lube oil pump, Lube oil filter, Lube
radiator
-
oil
consumption ≤1.36g/kw.h
-
cooling
system Water cooling method
-
air
intake system Filter
-
Exhaust
system Silencer
-
Starting
system 12 motor starting
5)
Alternator
-
Alternator
model BCI 184E
-
Alternator
manufacture WUXI NEWAGE STAMFORD
-
Protection
degree IP22
-
Poles
3-phase 4-wire
-
Insulation
class H
-
Winding
connection Y
-
Voltage
regulation AVR
-
Overload
strength 110% for 1 hour
6)
Switchboard Model:
-
Switchboard
model YF series
-
Voltage
400V
-
Control
panel device GTR-16 Control panel
-
Functions
Over speed (Alarm /Engine stop), High water temp (Alarm /Engine
stop), Low lubricating oil pressure
4.
ZX-16 Control Box:
ZX-16
Control box is control box for
generator which takes the GTR-16 controller as the core. It can
automatically start the generator and continue power supply , when
the power supply of city doesn’t work as usual .And when the city
power supply works normally ,it automatically stops working. If
there is some wrong with the generator, it also can stop working
itself and the trouble of generator will display on the control box
by LEO light. The alternating part is shock proofing meter which is
product of Chinese-foreign joint venture, direct current part is
meter of Zhong kang.
Merit
The
design of controller is very easy, so it is convenience to operate.
You can use on-off behind the controller to concoct the parameter.
Contact
signal input of ZX16 controller box switch
-
220V
alternating frequency
-
water
temperature on-off & induction
-
oil
pressure on-off & induction
-
low
voltage
-
minus
signal of automatic start-up
Switch
contact output signal
-
start
motor
-
accelerograph
-
full
magnetism
-
give
the alarm
-
former
place warm-up
Specification
Brief
introduction of operation
manual
operation: When confirm that the oil
and water are normal, turn the on-off to the automatic point, and
generating set will start, if there is no frequency after ten
seconds , stop the engine and after ten seconds start again .If
three times you can’t start ,the controller will automatic lock up
and show the failure of start; If the controller starts, then the
data about voltage, frequency, electric current , oil, water
temperature will display on the meter.
|